CHNT CHINT NXB-63 2P AC 230/400V Miniature Circuit Breaker C 6 10 16 20 25 32 40 63A Overload Protector DZ47 MCB Air Switch
- I am an international seller
Our shop sells the most popular 3C consumer electronics products,such as mobile phone accessories,computer accessories,game peripherals,smart wearables,and follow the most popular fashion trends. If you like our products,please follow us,become our follower and fan.We will provide you with the most popular products to satisfy your fashion shopping experience.NXB-63 1P type C LINK
NXB-63 2P type C LINK
NXB-63 3P type C LINK
NXB-63 4P type C LINK
1. Compliant standards
IEC60898-1
2. Major function
Overload protection, short circuit protection, positive isolation
3. Technical
Rated current: 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A; Rated voltage: 230V (1P, 1P+N), 230/400V (2 ~ 4P, 3P+N); Frequency: 50; Electromagnetic release type: C Number of poles: 1P, 1P+N, 2P, 3P, 3P+N, 4P; Mechanical life: 20000 cycles; Electrical life: 10000 cycles; Rated short-circuit breaking capacity(Icn): 6000A; Short-circuit breaking capacity (Ics): 6000A; Rated impulse withstand voltage (Uimp): 4kV; Power consumption on each pole of the circuit breaker: see Table 1.
Table 1
Rated current In (A) Maximum power consumption per pole (W)
1~10 3
16 3.5
20~25 4
32 6
40 7.5
50 9
63 13
4. Dimensions and installation sizes
Strong adaptability to environment and reliable operation in harsh environment
-30℃~70℃ ambient temperature range, to meet the needs of various applications
Contact indicator window, clear position
All models of contact head position visualization, avoid wrong operation, use more reliable
Circuit breaker and leakage protection choose
1.The main switch of the household distribution box is usually a 32A-63A mini circuit breaker or leakage protection circuit breaker which can disconnect the phase line and neutral line at the same time 2.10A-16A miniature circuit breaker is generally selected for lighting circuit 3.Socket circuit generally selects 16A-20A leakage protection circuit breaker
Switch current is selected according to equipment power
1.Calculation formula = power/voltage *3 (impact current) 2.For example: 3000W equipment 380V voltage select circuit breaker, 3000W*3 (impulse current) /380V≈ 23.68A ≈25A, we choose 25A circuit breaker or leakage circuit breaker
How to choose the type C and type D electromagnetic trip
The delay action range of type C is 5in-10in; The delay action range of type D is 10in-12in.(In is the rated current of the switch) Type C is used in light load areas such as distribution control and lighting.Type D can be used in heavy load starting places, such as motor starting, can avoid the equipment after starting the instantaneous current is too large to cause unnecessary overload switch trip.
Can't shut down
1.Whether the load port is short circuited 2.Operating mechanism failure 3.The rated current of the circuit breaker does not match the load current
High temperature
1.The wiring screw is loose without tightening the wire 2.The chosen wire section area is too small, the wire is too thin
Not disconnected in short circuit
1.The selected circuit breaker does not match the working conditions of the load
No electricity
1.Too little lead head stripping 2.The wiring screw is loose without tightening the wire
If you have any other questions, please contactcustomer service or leave a message